Description
Standing for high rate, the HR series is designed to provide power backup for smaller output applications like those found in personal or business power backup applications. The HR family is VRLA-AGM construction, which means the battery is maintenance free, no need to add water and able to be installed in multiple physical orientations without affecting service life.
- Wafer-thin plate technology combined with special proprietary formula utilizing 99.99% pure lead ingot in production for lead oxide, lead plate grids, and other lead components.
- Design life of up to 5 years in standby service.
- Optional flame-retardant ABS case construction.
- UL recognized under UL 1989 (file number MH14533).
- Comply with IATA/ICAO Special Provision A67 for air transport, are classified per MG Amendment 27 as a non-hazardous material for water transport, and recognized by DOT as “Dry charge” 49 CFR 171-189 for surface transport.
Cells Per Unit 6
Voltage Per Unit 12 V
Capacity 27W @ 15 minute-rate to 1.67V per cell @ 25°C (77°F)
Weight Approx. 1.97kg. (4.34 lbs.)
Internal Resistance Approx. Approx. 19.9mΩ
Operating Temperature Range Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25°C ± 3°C (77°F ± 5°F)
Float charging voltage 13.5 to 13.8 VDC/unit Average at 25°C (77°F)
Recommended Maximum Charging current limit 2.1A
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25°C (77°F)
Self Discharge It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25℃
Terminal F1/F2-Faston Tab187/250
Container Material ABS(UL94-HB) & Flammability resistance of(UL94-V0) can be available upon request.